Eaton 5PX removes power every 24 hours

When I powered on my UPS yesterday, I predicted when it would power off: 24 hours later. To be clear, it’s removing power from the outlets and not sending any notifications to the hosts that it’s about to do so.

Today, I captured the console when resetting and trying to power on the UPS.

The reset

This is the reset output:

Enter password to activate Maintenance Menu :
*******
Enter password to activate Maintenance Menu :
******

-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
        1 : Reset
        2 : Network configuration
        3 : Set Login Password to Default
        4 : Return to Default Configuration
        0 : Exit
-----------------------------------------------------------------------------


-----------------------------------------------------------------------------
Reset
-----------------------------------------------------------------------------
        1 : Restart the card from the boot
        0 : Exit
-----------------------------------------------------------------------------


-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
BOOTLOADER VERSION : EA
-----------------------------------------------------------------------------
RAM autotest in progress.
RAM autotest SUCCESS.

Commercial reference : NetworkMS
Kitting technical level : 15
Kitting revision : HE
Ethernet MAC Address : 00:20:85:F5:71:E0
Serial number : 301C24618

PHY autotest SUCCESS
FLASH autotest SUCCESS.

Decompress application in RAM
Run the application

Press a key to display the Rescue Menu


-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
USER APPLICATION VERSION : HF
-----------------------------------------------------------------------------
Network connection with static IP mode...

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0
Network configuration succeded
Parse the Configuration descriptor
Start the Web Server in HTTP mode (0).
Eaton XCPTEST - XCP Driver v1.2.0.1
Build date: Jun  1 2012 09:13:37
Acquisition of the UPS database declaration
In vThreadNotifUdp, sendto retuns ERROR 2 (network cable not connected)
XCP_Connect2 {COM1} Errorcode: XCPERR_CONNNOTOPEN
Calling XCP_Disconnect()
Connecting with SHUT to the UPS
Local database creation
Local database initialisation
Protocol available : TELNET with MENU
No environment sensor detected
End of Init, card is ready ...

Enter password to activate Maintenance Menu :
Warning: for SMTP server resolution don't forget to set DNS
File RAM0/ConfigurationData.xml created with 17660 bytes
File RAM0/ConfigurationData.xml written in Flash with 17660 bytes

At this point, I waited. With no more output for 3+ minutes, I pressed and held the power button.

Power button on

This is what appeared on the screen next, some errors, followed by reboot:

- state_bind_error -
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), shutHostGetReport too many fail - reset NMC 0


-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
BOOTLOADER VERSION : EA
-----------------------------------------------------------------------------
RAM autotest in progress.
RAM autotest SUCCESS.

Commercial reference : NetworkMS
Kitting technical level : 15
Kitting revision : HE
Ethernet MAC Address : 00:20:85:F5:71:E0
Serial number : 301C24618

PHY autotest SUCCESS
FLASH autotest SUCCESS.

Decompress application in RAM
Run the application

Press a key to display the Rescue Menu


-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
USER APPLICATION VERSION : HF
-----------------------------------------------------------------------------
Network connection with static IP mode...

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0
Network configuration succeded
Parse the Configuration descriptor
Start the Web Server in HTTP mode (0).
Eaton XCPTEST - XCP Driver v1.2.0.1
Build date: Jun  1 2012 09:13:37
Acquisition of the UPS database declaration
In vThreadNotifUdp, sendto retuns ERROR 2 (network cable not connected)
XCP_Connect2 {COM1} Errorcode: XCPERR_CONNNOTOPEN
Calling XCP_Disconnect()
Connecting with SHUT to the UPS
Local database creation
Local database initialisation
Protocol available : TELNET with MENU
No environment sensor detected
End of Init, card is ready ...

Enter password to activate Maintenance Menu :
Warning: for SMTP server resolution don't forget to set DNS
File RAM0/ConfigurationData.xml created with 17660 bytes
File RAM0/ConfigurationData.xml written in Flash with 17660 bytes

Trying again

I pressed and held the button for varying lengths of time. After a 10s press, we got this, again:

- state_bind_error -
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), shutHostGetReport too many fail - reset NMC 0


-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
BOOTLOADER VERSION : EA
-----------------------------------------------------------------------------
RAM autotest in progress.
... etc

What does “work”

If I press and hold the button now, while the above booting continues, the outlets get power. For 24 hours, then they’ll go out again.

The rest of the boot process

This is the rest of boot process from above.

RAM autotest SUCCESS.

Commercial reference : NetworkMS
Kitting technical level : 15
Kitting revision : HE
Ethernet MAC Address : 00:20:85:F5:71:E0
Serial number : 301C24618

PHY autotest SUCCESS
FLASH autotest SUCCESS.

Decompress application in RAM
Run the application

Press a key to display the Rescue Menu


-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
USER APPLICATION VERSION : HF
-----------------------------------------------------------------------------
Network connection with static IP mode...

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0
Network configuration succeded
Parse the Configuration descriptor
Start the Web Server in HTTP mode (0).
Eaton XCPTEST - XCP Driver v1.2.0.1
Build date: Jun  1 2012 09:13:37
Acquisition of the UPS database declaration
In vThreadNotifUdp, sendto retuns ERROR 2 (network cable not connected)
XCP_Connect2 {COM1} Errorcode: XCPERR_CONNNOTOPEN
Calling XCP_Disconnect()
Connecting with SHUT to the UPS
Local database creation
Local database initialisation

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
Protocol available : TELNET with MENU
No environment sensor detected
End of Init, card is ready ...

Enter password to activate Maintenance Menu :
File RAM0/ConfigurationData.xml created with 17660 bytes
File RAM0/ConfigurationData.xml written in Flash with 17660 bytes
Warning: for SMTP server resolution don't forget to set DNS
RAM autotest SUCCESS.

Commercial reference : NetworkMS
Kitting technical level : 15
Kitting revision : HE
Ethernet MAC Address : 00:20:85:F5:71:E0
Serial number : 301C24618

PHY autotest SUCCESS
FLASH autotest SUCCESS.

Decompress application in RAM
Run the application

Press a key to display the Rescue Menu


-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
USER APPLICATION VERSION : HF
-----------------------------------------------------------------------------
Network connection with static IP mode...

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0
Network configuration succeded
Parse the Configuration descriptor
Start the Web Server in HTTP mode (0).
Eaton XCPTEST - XCP Driver v1.2.0.1
Build date: Jun  1 2012 09:13:37
Acquisition of the UPS database declaration
In vThreadNotifUdp, sendto retuns ERROR 2 (network cable not connected)
XCP_Connect2 {COM1} Errorcode: XCPERR_CONNNOTOPEN
Calling XCP_Disconnect()
Connecting with SHUT to the UPS
Local database creation
Local database initialisation

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
Protocol available : TELNET with MENU
No environment sensor detected
End of Init, card is ready ...

Enter password to activate Maintenance Menu :
File RAM0/ConfigurationData.xml created with 17660 bytes
File RAM0/ConfigurationData.xml written in Flash with 17660 bytes
Warning: for SMTP server resolution don't forget to set DNS

My plan

I’m going to leave my laptop attached overnight and see what appears on the console.

2025-01-13: The next day

At about 11:50 AM, I ran a battery test. The UPS removed power from the outlets. This is what I saw on the console:

- state_bind_error -
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), GetReport tx_event_flags_set() retuns ERROR 1
In threadBinding(), shutHostGetReport too many fail - reset NMC 0
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0


-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
BOOTLOADER VERSION : EA
-----------------------------------------------------------------------------
RAM autotest in progress.
RAM autotest SUCCESS.

Commercial reference : NetworkMS
Kitting technical level : 15
Kitting revision : HE
Ethernet MAC Address : 00:20:85:F5:71:E0
Serial number : 301C24618

PHY autotest SUCCESS
FLASH autotest SUCCESS.

Decompress application in RAM
Run the application

Press a key to display the Rescue Menu


-----------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
USER APPLICATION VERSION : HF
-----------------------------------------------------------------------------
Network connection with static IP mode...

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
IAM - lost STATIC IPv4 address 10.52.0.184 on interface eth0
Network configuration succeded
Parse the Configuration descriptor
Start the Web Server in HTTP mode (0).
Eaton XCPTEST - XCP Driver v1.2.0.1
Build date: Jun  1 2012 09:13:37
Acquisition of the UPS database declaration
In vThreadNotifUdp, sendto retuns ERROR 2 (network cable not connected)
XCP_Connect2 {COM1} Errorcode: XCPERR_CONNNOTOPEN
Calling XCP_Disconnect()
Connecting with SHUT to the UPS
Local database creation
Local database initialisation

IP configuration :
        IP address : 10.52.0.184
        Subnet mask : 255.255.255.0
        Gateway : 10.52.0.1
Protocol available : TELNET with MENU
No environment sensor detected
End of Init, card is ready ...

Enter password to activate Maintenance Menu :
File RAM0/ConfigurationData.xml created with 17660 bytes
File RAM0/ConfigurationData.xml written in Flash with 17660 bytes
Warning: for SMTP server resolution don't forget to set DNS

So. The batteries, despite being reported as 100%, aren’t up to the task.